ماركة | Salicru |
---|---|
الاستطاعة | 20kVA |
UPS Type | Online |
- MODEL: SLC CUBE3+
- TECHNOLOGY: On-line, double conversion, HF, DSP control
- INPUT: Nominal voltage:
Single-phase 120 / 127 / 220 / 230 / 240 V
Three-phase 3 x 208 / 3 x 220 / 3 x 380 / 3 x 400 / 3 x 415 V (3P + N)
- Voltage margin: +15% / -20% (configurable)
- Frequency: 50 / 60 Hz
- Total Harmonic Distortion (THDi):
20 kVA 100% load: <1.5% / 50% load: <2.5% / 10% load: <6.0% - Power factor: 1 from 10% load
- Rectifier topology Three-phase IGBT full wave, soft start, PFC, transformerless
- OUTPUT Nominal voltage
(1) Single-phase 120 / 127 / 220 / 230 / 240 V
Three-phase 3 x 208 / 3 x 220 / 3 x 380 / 3 x 400 / 3 x 415 V (3P + N)
- Accuracy State ± 1% steady / ± 2% dynamic
- Response time 20 ms for load steps 0% ÷ 100% and voltage drop up to -5%
- Frequency Synchronised 50/60 Hz ±5 Hz (selectable)
- Free running 50/60 Hz ±0.05%
- Maximum synchronisation speed From 1 Hz/s to 10 Hz/s (programmable)
- Total Harmonic Distortion (THDv)
Linear load <0.5%
Nonlinear load 7.5 ÷ 80 kVA: <1.5% / 100 ÷ 200 kVA: <2% (EN-62040-3) - Output Power Factor 0.9
- Admissible overload 125% for 10 min / 150% for 60 s
- Admissible crest factor >3:1
- Total efficiency in On-line mode 7.5÷60 kVA: 92.0%÷93.0% / 80÷200 kVA: 94.0%÷95.0%
- Efficiency in Smart Eco-mode Up to 98,4%
- STATIC BYPASS Type and activation criteria Solid state, controlled by microprocessor
- Transfer time On-line mode Nil
- Smart Eco-mode 4 ms (typical)
- Transfer to bypass Immediate, for overloads exceeding 150%
- Retransfer Automatic, after alarm deactivation
- MANUAL BYPASS Type Without interruption
- BATTERIES Type (standard) Lead acid, sealed, maintenance free
- Charge voltage regulation Batt-Watch
- COMMUNICATION Ports 1 x RS232/RS485 + 1xUSB, with Modbus protocol
- Interface to relays 4 x AC failure, bypass, low battery and general
- Free slots 1, for SNMP/SICRES
- Parallel connection 2 x connectors
- GENERAL Operating temperature 0° C ÷ +40° C
- Relative humidity Up to 95%, non-condensing
- Operating altitude 2,400 masl
- Acoustic noise at 1 metre <52 dB(A) (2)
- STANDARDS Safety EN-62040-1-2; EN-60950-1
- Electromagnetic Compatibility (EMC) EN-62040-2
- Operating VFI-SS-111 according to EN 62040-3
- Quality and Environmental Management ISO 9001 and ISO 14001
لا يوجد تقييمات بعد.